Description
PH Controller Dosing Pump
The setting of Hi and Low Level of pH Value to operate Dosing Pump: PH Controller Dosing Pump
Lower Level Dosing Pump / Alarm Setting: Press REED button lower side rotate screw provided on the right side to set lower-level alarm/relay output if pH Value of solution goes down to this value relay 1 will turn ON and provide its potential-free contact as output.
Higher Level Dosing Pump / Alarm Setting: Press REED button upper side rotate screw provided on the right side to set Higher level alarm/relay output if pH Value of solution goes higher to this value relay 2 will turn ON and provide its potential-free contact as output.
PH Controller Dosing Pump
a) Press the SET button Upper display show HPH the higher limit to set
and lower display shows the value of HPH already set
Press UP and DN buttons to set Higher Limit
b) Press the SET button once again Upper display shows LPH the lower limit to set
and lower display shows the value of LPH already set
Press UP and DN buttons to set Lower Limit
c) Press the SET button again to Set Delay Time DELY in Minutes. It works if pH Value
goes more than HPH or less Than LPH value than Dosing will Start after this delay
for a set value of Quantity in ML, after dosing it will further wait for monitoring pH Value
before next dosing.PH Controller Dosing Pump
d) press SET button once again to set Dosing Quantity in ML
if pH Value goes higher from HPH or lowers from LPH then concerned dosing pump will
dose this set ML quantity in solution and wait for DELY time and Monitor the pH Value
of Solution if pH value not found within Set Limits ie. Between HPH and LPH limits
then after waiting time above process will repeat again and again till pH value stables
e) Press SET Button again or ENT button to save the changes
else change will remove after power OFF
PH Controller Dosing Pump
While we calibrate the pH meter or pH Controller. Hence we have to follow the following steps carefully.
1. Wash the Probe in Distilled water and then Dip in a Buffer solution of 7 pH
wait till the pH value is Stable, Press the UP button, wait to calibrate
2. Wash the probe in distilled water and then Dip in a Buffer solution of 4 pH
wait till the pH value is stable, Press the DN button, wait to calibrate
Auto CALIBRATION OF 4pH AND 7 pH
While you want to calibrate the pH Controller as per factory setting. Hence Just Push SET and ENT buttons at once calibration will set to factory set value
Specification : digital-ph-controller-india
- Range : 0.00 to 14.0 pH
- Resolution : 0.10 pH
- Tolerence : +/- 0.10 pH
- Input: pH Probe any Brand BNC Connector
- Set Point 2 Nos for Upper Limit and Lower Limit
- Output : 2 Potential free Relay Output
- Calibration: Auto Calibration Push Buttons on Front Panel; 4pH and 7pH Value
- Display: Seven-Segment Bright LED Display
- Operating Voltage: 220 Vac
- Size : 96 * 96 * 110
- Body: PP/ABS
Types of pH Meters
Hence we supply a wide range of pH Meters. While use and application are different. We Introduce here 6 types of pH Meters; So please click on link given here 1 to 6; if you want to โKnow More aboutโ any product; and technical specifications. While โclick hereโ; if you are interested to know more products in this range.digital-ph-controller-india
- Digital pH Meterย : Online Panel Mounted with 2 point calibration.
- Online pH Meter :ย ย with 0 to 10 volt analog outputย and 2 point calibration
- Digital pH Meterย :ย with 0-20 MA outputย and 2 point calibration
- Digital pH Meterย : with 485 Modbus protocol and 2 point calibration
- pH Meterย Table Top : for Laboratoryย useย and 2 point calibration
- Sensor / Probe / Electrode for pH Meter / pH Controller
pH Controller distributor and supplier : digital-ph-controller-india
Hence we are supplier / dealer of Digital pH Controller Online. We have many type of pH Meter as well as Controller. We design there meters as per your requirement. Hence please click the link;ย given below to Reed more about given products. Or โClick Hereโ; to see more products in this category. digital-ph-controller-india
- Onlineย pH Controller with 2 Point Calibration, 1 Set Pointย and Single Relay output
- Digitalย pH Controller with 2 Point Calibrationhttps://ph-meter.online/, 2 Set Point and 2 Relayย output
- Onlineย pH Controller Online with 2 Point Auto Calibration, 2 Set Point andย 2 Relay output
- pH Controller Online with 2 Point Auto Calibration, 2 Set Point andย 2 Relay output,ย Dosing Quantity and Analysis Time Setting
Join us as aย Dealer & Distributor in your city India. Hence we also promise doorstep delivery of the products without any delays. To place an order; or send your inquiry or call now “8178668698”. Our experts would be glad to assist you.
Reviews
There are no reviews yet.